IEC61850/IEEE1613 Hardened 10/100BASE-TX to 100BASE-FX Media Converter

 

  • Complies with IEC61850 EMC and Environment requirement, and IEEE1613 standard for substation and power automation
  • Complies with EN50121-4 EMC requirement for Railway applications
  • Complies with NEMA TS1 & TS2 Environmental requirements for Traffic control equipment
  • DIP switch configuration for "Link-Fault-Pass-Through," link down alarm, speed, duplex mode
  • 768K bits buffer memory
  • 10/100Mbps-Full/Half-duplex, Auto-Negotiation, Auto-MDI/MDIX
  • Full wire-speed forwarding rate
  • Alarms for power and port link failure by relay output
  • Redundant power inputs with Terminal Block and DC Jack
  • -40°C to 75°C (-40°F to 167°F) operating temperature range
  • Hardened aluminum case
  • Supports DIN-Rail, Panel or Rack Mounting installation

 

Technology

Standards
IEEE802.3 10BASE-T,IEEE802.3u 100BASE-TX/100BASE-FX, IEEE802.3x
 

Forward and Filtering Rate
14,880pps for 10Mbps
148,810pps for 100Mbps
 

Packet Buffer Memory
768K bits
 

Processing Type
Store-and-Forward
Half-duplex back-pressure and IEEE802.3x full-duplex flow control
 

Power

Input
Input Voltage: 12 to 48VDC (Terminal Block)/12VDC(DC Jack)
 

Power Consumption
2.4W MAX. 0.2A @ 12VDC, 0.05A @ 48VDC
 

Overload Current Protection
Present
 

Reverse Polarity Protection
Present
 

Mechanical

Casing
Aluminum case
IP30
 

Dimensions
50mm (W) x 110mm (D) x 135mm (H)
(1.97" (W) x 4.33" (D) x 5.31" (H))
 

Weight 0.8Kg (1.76lbs.)
 

Installation
DIN-Rail (Top hat type 35mm), Panel, Rack Mounting
 

Interface

Ethernet Port
10/100BASE-TX: 1 port
100BASE-FX: 1 port
 

LED Indicators
Per Unit:Power Status (Power 1, Power 2, Fault),Link-Fault-Pass-Through
Per Port: 10/100TX: Link/Activity, Full-duplex/Collision,Speed
100FX: Link/Activity, Full-duplex/Collision
 

Relay Contact
Relay contact rating with current 1A @ 30VDC,0.5A @ 120VAC
 

Environment

Operating Temperature
-40°C to 75°C (-40°F to 167°F)
Tested @ -40°C to 85°C (-40°F to 185°F)
 

Storage Temperature
-40°C to 85°C(-40°F to 185°F)
 

Ambient Relative Humidity
5% to 95% (non-condensing)
 

Regulatory Approvals

ISO
Manufactured in an ISO9001 facility
 

Safety
UL508
 

EMI
FCC Part 15, Class A
EN61000-6-4
- EN55022
- EN61000-3-2
- EN61000-3-3
 

EMS
IEC61850-3 & IEEE1613: Substation & Power automation Applications
EN50121-4: Railway Applications
EN61000-6-2
- EN61000-4-2 (ESD Standards)
Contact: + / - 8KV; Criteria B
Air: + / - 15KV; Criteria B
- EN61000-4-3 (Radiated RFI Standards)
35V/m, 80 to 1000MHz; 80% AM Criteria A
- EN61000-4-4 (Burst Standards)
Signal Ports: + / - 4KV; Criteria A
D.C. Power Ports: + / - 4KV; Criteria A
- EN61000-4-5 (Surge Standards)
Signal Ports: + / - 2KV; Line-to-Line; Criteria A
D.C. Power Ports: + / - 2KV; Line-to-earth; Criteria A
- EN61000-4-6 (Induced RFI Standards)
Signal Ports: 10Vrms @ 0.15 - 80MHz; 80% AM Criteria A
D.C. Power Ports: 10Vrms @ 0.15 - 80MHz; 80% AM
Criteria A
- EN61000-4-8 (Magnetic Field Standards)
1000A/m @ 50, 60Hz; Criteria A
 

Environmental

Test Compliance
IEC60068-2-6 Fc (Vibration Resistance)
5g @ 10 - 150Hz, Amplitude 0.35mm (Operation/Storage/Transport)
IEC60068-2-27 Ea (Shock)
25g @ 11ms (Half-Sine Shock Pulse; Operation)
50g @ 11ms (Half-Sine Shock Pulse; Storage/Transport)
IEC60068-2-32 Ed (Free Fall)
1M (3.281ft.)

 

EL1141-X0Z
10/100BASE-TX to 100BASE-FX Hardened Media Converter

(X) =
1: Multi Mode (SC)
2: Multi Mode (ST)
A: Single Mode (SC) -20Km
B: Single Mode (SC) -40Km
H: Single Mode (ST) -20Km
6: Multi Mode (SC) WDM -TX:1310nm/RX:1550nm -2Km
7: Multi Mode (SC) WDM -TX:1550nm/RX:1310nm -2Km
8: Multi Mode (SC) WDM -TX:1310nm/RX:1550nm -5Km
9: Multi Mode (SC) WDM -TX:1550nm/RX:1310nm -5Km
P: Single Mode (SC) WDM -TX:1310nm/RX:1550nm -20Km
Q: Single Mode (SC) WDM -TX:1550nm/RX:1310nm -20Km
R: Single Mode (SC) WDM -TX:1310nm/RX:1550nm -40Km
S: Single Mode (SC) WDM -TX:1550nm/RX:1310nm -40Km
*More 100FX Fiber Options also available upon request.
 

Power Supply: (Optional)
*Option - The Terminal Block type external power supply are not included. Please order the following part numbers, as required:
DR-30-24, DR-60-24, DR-75-24, DR-120-24 or 41-136046-X X=1,2,3,4,5
 

Installation Type:

DIN Rail (mounting kit is included)
Optional Panel mount kit, part number: KP-AA96-480